Potential Transformer for SF6 Gas-Insulated MOF Panel


Potential Transformer for SF6 Gas-Insulated MOF Panel

EPF-20SH

Intended for power companies, this indoor single-phase epoxy-cast potential transformer is designed to be mounted inside the SF6 gas-insulated MOF (Metering Outfit) panel of a 25.5 kV (max.) power system. With an added tap in the secondary winding, this PT can offer two voltage ratios (120/60:1).


About the Product

Intended for power companies, the EPF-20SH single-phase potential transformer is designed to be mounted inside the SF6 gas-insulated MOF (Metering Outfit) panel of a 25.5kV (max.) power system. With an added tap in the secondary winding, this PT can offer two voltage ratios (120/60:1) and allows easy switching between the two, while maintaining the accuracy and burden rating of 0.3Y at each voltage ratio. Insulated with Araldite® epoxy resin, this indoor potential transformer offers excellent electrical performance and high reliability.

Specifications

  • Indoor usage; epoxy cast (epoxy resin)
  • Standard: IEEE
  • System Voltage: 25.5 kV or below
  • Frequency: 50 / 60 Hz
  • Intended for a SF6 gas-insulated MOF panel
  • Nominal Voltage Ratio: 120/60:1 (two voltage ratios)
  • Accuracy and Burden: 0.3Y
  • Approximate Weight: 57 kg

Selection Table

Model

Primary Voltage

Secondary Voltage

Accuracy / Burden

AC / BIL

EPF-20SH

23.90/√3 kV  /  11.95/√3 kV

115V

0.3Y / 0.3Y

50/125 kV

Related Products
  • Current Transformer for SF6 Gas-Insulated MOF Panel
    Current Transformer for SF6 Gas-Insulated MOF Panel
    MOF-24

    For power companies. To be mounted inside the SF6 gas-insulated MOF panel of a 25.5 kV (max) power system. With 2 primary coils, this current transformer offers 2 current ratios while maintaining the required accuracy and burden rating at each current ratio. Insulated with Araldite® epoxy resin.


  • Outdoor-Type Potential Transformers for Billing (Epoxy-Cast)
    Outdoor-Type Potential Transformers for Billing (Epoxy-Cast)
    VPF Series

    Cast in Araldite® UV-resistant cycloaliphatic epoxy resin, these medium-voltage potential transformers for billing are designed for long-term outdoor use in harsh conditions such as solar ultraviolet radiation, salt fog, high temperature, and high humidity. Designed to be part of a Metering Outfit (MOF).


  • Dry-Type Bushing Current Transformers for GIS or Power Transformers
    Dry-Type Bushing Current Transformers for GIS or Power Transformers
    TB-1M Series

    Suited to power transmission and distribution systems and intended to work with measuring or monitoring instruments, or with protective relays, these bushing CTs (BCTs) can also be used with GIS or in conjunction with power transformers bushings. Insulation tape or epoxy resin as insulation material.


  • Current Transformers / Extended Range Current Transformers (ERCTs) for Billing, 10~30kV Outdoor Type
    Current Transformers / Extended Range Current Transformers (ERCTs) for Billing, 10~30kV Outdoor Type
    AWF Series

    Used for power monitoring or as part of an MOF (Metering Outfit) for a 12~36kV power system, these outdoor CTs for billing are insulated with Araldite® UV-resistant cycloaliphatic epoxy. Accuracy 0.15S~0.3; burden B-0.5. Available as Extended Range Current Transformers (ERCTs) if requested.



Download Materials

  • Tag
  • Instrument Transformers
  • PT
  • CT PT
  • VT
  • MV Potential Transformers
  • MV Voltage Transformers
  • Medium-Voltage Potential Transformers
  • Medium-Voltage Voltage Transformers
  • Medium Voltage Voltage Transformers
  • Medium Voltage Potential Transformers
  • MV PTs
  • MV VTs
  • Metering Out Fit
  • Metering Out-Fit