Potential Transformer for SF6 Gas-Insulated MOF Panel
EPF-20SH
Intended for power companies, this indoor single-phase epoxy-cast potential transformer is designed to be mounted inside the SF6 gas-insulated MOF (Metering Outfit) panel of a 25.5 kV (max.) power system. With an added tap in the secondary winding, this PT can offer two voltage ratios (120/60:1).
About the Product
Intended for power companies, the EPF-20SH single-phase potential transformer is designed to be mounted inside the SF6 gas-insulated MOF (Metering Outfit) panel of a 25.5kV (max.) power system. With an added tap in the secondary winding, this PT can offer two voltage ratios (120/60:1) and allows easy switching between the two, while maintaining the accuracy and burden rating of 0.3Y at each voltage ratio. Insulated with Araldite® epoxy resin, this indoor potential transformer offers excellent electrical performance and high reliability.
Specifications
- Indoor usage; epoxy cast (epoxy resin)
- Standard: IEEE
- System Voltage: 25.5 kV or below
- Frequency: 50 / 60 Hz
- Intended for a SF6 gas-insulated MOF panel
- Nominal Voltage Ratio: 120/60:1 (two voltage ratios)
- Accuracy and Burden: 0.3Y
- Approximate Weight: 57 kg
Selection Table
Model |
Primary Voltage |
Secondary Voltage |
Accuracy / Burden |
AC / BIL |
EPF-20SH |
23.90/√3 kV / 11.95/√3 kV |
115V |
0.3Y / 0.3Y |
50/125 kV |
- Related Products
-
-
Current Transformer for SF6 Gas-Insulated MOF Panel
MOF-24
For power companies. To be mounted inside the SF6 gas-insulated MOF panel of a 25.5 kV (max) power system. With 2 primary coils, this current transformer offers 2 current ratios while maintaining the required accuracy and burden rating at each current ratio. Insulated with Araldite® epoxy resin.
-
Outdoor-Type Potential Transformers for Billing (Epoxy-Cast)
VPF Series
Cast in Araldite® UV-resistant cycloaliphatic epoxy resin, these medium-voltage potential transformers for billing are designed for long-term outdoor use in harsh conditions such as solar ultraviolet radiation, salt fog, high temperature, and high humidity. Designed to be part of a Metering Outfit (MOF).
-
Dry-Type Bushing Current Transformers for GIS or Power Transformers
TB-1M Series
Suited to power transmission and distribution systems and intended to work with measuring or monitoring instruments, or with protective relays, these bushing CTs (BCTs) can also be used with GIS or in conjunction with power transformers bushings. Insulation tape or epoxy resin as insulation material.
-
Current Transformers / Extended Range Current Transformers (ERCTs) for Billing, 10~30kV Outdoor Type
AWF Series
Used for power monitoring or as part of an MOF (Metering Outfit) for a 12~36kV power system, these outdoor CTs for billing are insulated with Araldite® UV-resistant cycloaliphatic epoxy. Accuracy 0.15S~0.3; burden B-0.5. Available as Extended Range Current Transformers (ERCTs) if requested.
-
- Download Materials
-
-
Potential Transformer for SF6 Gas-Insulated MOF Panel (Model: EPF-20SH)
Easy-to-print document, containing product description, specifications, and a selection table.
-
CT & PT Selection Guide: How to Choose a Current Transformer or Potential Transformer
How to select, based on application and power system attributes, the primary and secondary currents, burden, accuracy, rated frequency, type (indoor vs. outdoor), insulation material, etc.
-