3.6 kV Current Transformer, Coil Molded
EW-3S
For measuring or monitoring instruments, this medium-voltage, indoor, coil molded current transformer is often used with the main panel or the motor control panel of a 3.6 kV (max.) power system. Insulated with Araldite® epoxy resin. Compact and easy to install.
Medium-Voltage Coil Molded Current Transformer
About the Product
Intended for measuring or monitoring instruments, this coil molded current transformer for indoor use is insulated with Araldite® epoxy resin. Often used with the main panel or the motor control panel of a 3.6kV (max.) power system, this current transformer is compact and easy to install. It features a fine exterior and excellent electrical performance.
Specifications
- Standard: IEC or IEEE*
- Indoor application
- Coil molded
- High-grade silicon steel core
- Rated Voltage: ≦ 3.6 kV
- Frequency: 50 or 60 Hz
- Ith = 16 kA/1S
- AC/BIL: 10/40kV
- Current Ratio: ≦ 400/5A
- Burden / Accuracy: 40VA/1.0
- Approximate Weight: 5 kg
Coil Molded Current Transformers (Selection Table)
Model | System | Primary | Secondary Current | Burden / Accuracy | Ith | AC/BIL | Approx. | Num. Of Cores | |
Core 1 | Core 2 | ||||||||
EW-3S | 3.6 kV | 10~400A | 5A / 1A | - | 40VA/1.0 | 16 kA/1S | 10/40 | 5 | 1 |
3.6 kV | 10~300A | 5A / 1A | 5A / 1A | 15VA/5P10 + 25VA/0.5 or 15VA/5P10+ 30VA/1.0 | 9 | 2 | |||
12 kV | 5~400A | 5A / 1A | - | 40VA/1.0 | 28/75 | 7 | 1 |
* Other standards and specifications available
- Download Documents
CIC Company Profile
Learn about our company: history, strengths, products, global locations, and our Advanced Electricity Lab.
【Product Brochure】Coil Molded Current Transformers, EW Series
Including EW-3S, EW-3C, and EW-10SH. Production description, photos, and a selection table.
【Product Dimensions】Coil Molded Current Transformers, EW-3S Series
Download PDF for basic drawing(s) and dimensions of this product. For more detailed information, please contact CIC.
CT & PT Selection Guide: How to Choose a Current Transformer or Potential Transformer
How to select, based on application and power system attributes, the primary and secondary currents, burden, accuracy, rated frequency, type (indoor vs. outdoor), insulation material, etc.
- Related Products
Coil Molded Current Transformer with Cut Core, 12 kV
EW-10SH
Cut-core, medium-voltage, indoor-use, coil molded current transformer intended for a 12 kV (max.) power system and suited for measuring or monitoring instruments. Insulated with Araldite® epoxy resin.
Two-Core Coil Molded Current Transformer with Cut Cores, 3.6 kV
EW-3C
2-core (core type: cut-core), medium-voltage coil molded current transformer. Often used with the main panel or the motor control panel of a 3.6 kV (max.) power system. Good for protection. Suited to measuring and monitoring instruments. Araldite® epoxy resin.
Coil Molded Single-Phase Voltage Transformers (Potential Transformers), Indoor Use
EP-3SF/6SF Series
Voltage transformers of the EP-3SF/6SF Series are coil-molded, single-phase, indoor-type, medium-voltage, epoxy-resin-insulated potential transformers suitable for power systems of 7.2kV or below. Made with either a laminated core (Model EP-3SF2) or a cut core (EP-3SF5 & EP-6SFK), the voltage transformer has two power fuses attached to the primary side. Specific models from this series can be used as an auxiliary power source for circuit breaker operation — that is, as a control power transformer (CPT), also referred to as a control transformer (CTR), industrial control transformer, or machine tool transformer.
Voltage Transformers (Potential Transformers) as Circuit Breaker Operation Power Source
EPF-3SF1, EPF-6SF2
Voltage transformers EPF-3SF1 and EPF-6SF2 are medium-voltage, indoor-type potential transformers cast in epoxy resin, commonly installed on switchgear (3.3kV or 6.6kV) to serve as an auxiliary power source* for circuit breaker operation. Positioned atop the switch as an operational power source, these transformers can handle relatively high outputs for short durations. Featuring Class-F heat-resistant insulation material for the coils, each voltage transformer is equipped with two power fuses on the primary side to safeguard against overload and short-circuit currents.* Auxiliary power source: In this application, the voltage transformer may also be referred to as a "control power transformer" (CPT), "control transformer" (CTR), "industrial control transformer," or a "machine tool transformer."
Three-Phase Grounding Voltage Transformer (GVT), or Grounding Potential Transformer (GPT), for MV Indoor Applications
EGP-3DF, EGP-6DF
This ground voltage transformer (GVT), or ground potential transformer (GPT), is a three-phase medium-voltage (MV) potential transformer for indoor applications. With a fuse for each phase, this PT (VT) features epoxy-insulated coils and a five-legged (five-limbed) laminated core. This voltage transformer is used with measuring or monitoring instruments, or for ground-fault protection.